Universal Comfort Products  
Home pageProduct guideOnline servicesContact us

Home page

Product guide:
Flexible ducts

Online services:

Contact us:



Failed to execute CGI : Win32 Error Code = 50
UPC #030:
25 ' Insulated UL 181 Class 1 Air Duct

Description:

ATCO's UPC #030 is a UL 181 Class 1 Air Duct and is manufactured with a reinforced metallized polyester jacket. The UPC #030 inner core is air-tight and is designed for low-to-medium operating pressures in HVAC systems.

Construction:

A double lamination of tough polyester which encapsulates a steel wire helix forms the air-tight inner core to ATCO's UPC #030. The double layer core is wrapped in a thick blanket of fiberglass insulation and sheathed in a rugged and durable reinforced metallized polyester jacket.

Applications:

UPC #030 is designed for indoor use as a supply and return air duct in residential and commercial low-to-medium pressure heating and air conditioning systems. ATCO's UPC #030 can be used as a complete air duct system and/or a branch duct connecting to mixing boxes, diffusers, light troffers, room inlets or other terminal devices.

Code Compliance:

UL 181, UMC 10-1, SBCC, BOCA, NFPA 90A & 90B, HUD 515-2.1 (a) (b), Cities of Chicago, New York & San Francisco, County of Dade (Florida), California State Fire Marshal.

Product Data:
    Length: 25'.

    Diameters: 4", 5", 6", 7", 8", 9", 10", 12", 14", 16", 18", 20".

    Vapor Barrier: Reinforced metallized polyester.

    End Treatment: 25' - plain ends.

    Packaging: 1 piece per carton.
Performance Data:
    Rated Positive Pressure: 10" w.g. per UL-181 (UL Listed pressure ratings are determined in straight lengths @ ambient temperatures.) .

    Recommended Operating Pressures (Determined in a 90° bend at elevated temperatures in accordance with ADC FD 72-R1 Test Code.).

    Maximum Positive:.

    6" w.g. - 4" thru 12" Dia.
    4" w.g. - 14" thru 20" Dia.
    (With factory installed metal collars, 2" w.g. - all diameters).

    Maximum Negative: 3/4" w.g. - all diameters.

    Maximum Velocity: 5,000 FPM.

    Vapor Transmission: .05 perms.

    Maximum Operating Temperatures:

    -20° F to 140° F Continuous (@ maximum pressure)
    -20° F to 180° F Continuous (@ 2" pos. w.g. max.)
    -20° F to 250° F Intermittent (@ 8" pos. w.g. max.).

    R Value: 4.2 (In accordance with ADC flexible duct performance and installation standards (1991) using ASTM C-518 at installed wall thickness on flat insulation only.).

    Flame Spread: Less than 25.

    Smoke Developed: Less than 50.

Installation:

Air duct connections and joints shall be made per installation instructions outlined by ATCO Rubber Products, Inc. and as required by the UL 181 listing procedure. (Installation instructions are included inside of each carton.).

Air Friction Chart

Air Flow 'SCFM':

STRAIGHT RUN.

FD 72-R1 Test Code of the Air Diffusion Council. Friction loss is computed in inches of water gauge per 100 ft. of straight duct. By using CFM or FPM values for a given duct dimension, the friction loss can be determined. Conversion of CFM to FPM also can be made.




Flexible ducts

Insulated:
UPC#30.

Uninsulated: .


Webmaster © 2001 "Universal Comfort Poducts, inc."
Tel: 1-817-590-94-69